What size AC for Paris, TN? 3 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Paris needs

3 tons central AC or heat pump, about 32,300 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 30% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 3 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 743 square feet in this climate. For a single room, size by the room: 16.1 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Paris 2 Se (0.8 mi away). Jul is the hottest month, averaging a high of 88.2°F and a low of 67.7°F, with about 33 days a year at 90°F or more. That gives a design temperature of 93°F against 75°F inside.

What it costs to run

About 2,044 kWh a year at SEER2 14.3, or roughly $282 at Tennessee's average residential rate of 13.8¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Paris

Of the 32,300 BTU/hr, 12,960 comes through walls, roof and windows on a 93°F afternoon (40%), 13,000 is sun on the house (40%), 2,120 is four people and their appliances, and 4,200 is moisture the coil has to wring out of Paris's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 28,080 BTU/hr before the moisture allowance.

Other house sizes in Paris

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft17,4001.5 tons2 tons
1,500 sq ft24,8002 tons2.5 tons
2,500 sq ft39,8003.5 tons5 tons
3,000 sq ft47,2004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,400 BTU/hr; a 350 sq ft living room needs about 5,600 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,700 BTU/hr.

Month by month in Paris

MonthAvg highCooling degree daysAC kWh
Jan45.9°F01
Feb50.7°F11
Mar60°F710
Apr70.4°F3245
May77.9°F123171
Jun85.1°F292406
Jul88.2°F401558
Aug88.1°F379526
Sep82.3°F196272
Oct71.7°F3752
Nov59°F23
Dec49.1°F01

Jul alone uses 27% of the year's cooling energy. The unit runs the equivalent of 905 hours a year at full output.

Paris against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Murray, KY22 mi95°F3 tons
Martin, TN30 mi96°F3.5 tons
Union City, TN42 mi94°F3 tons
Jackson, TN53 mi96°F3.5 tons
Dickson, TN55 mi92°F3 tons
Clarksville, TN57 mi94°F3 tons

Of 65 Tennessee cities here, Paris has the 53rd highest cooling load. The range runs from Crossville at 27,300 BTU/hr to Memphis at 41,200.

Where Paris's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Paris 2 Se, 0.8 miles from the center of Paris at 443 ft above sea level. That is close enough that the station's summers are Paris's summers.

No other city in this set uses Paris 2 Se, so this sizing is Paris's alone.

The sun over Paris in late July

At 36.29°N, the noon sun on 21 July stands 74.1° above the horizon over Paris and the day runs 14 h 07 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

10,517 people live in Paris, the 63rd largest of the 65 Tennessee cities sized on this site. Coordinates used: 36.2927, -88.3081.

Paris AC sizing questions

What size AC does a 2,000 sq ft house in Paris, TN need?

About 3 tons, for a cooling load of 32,300 BTU/hr on a 93°F design day. That is one ton per 743 square feet in Paris's climate.

Is 20 BTU per square foot right for Paris?

The chart gives 3.5 tons for 2,000 sq ft, against 3 tons sized from NOAA's 1991 to 2020 normals at Paris 2 Se. For a single room here, plan on 16.1 BTU/hr per square foot.

What does central AC cost to run in Paris?

About $282 a year: 2,044 kWh at SEER2 14.3 and 13.8¢ per kWh, over 5 cooling months.