What size AC for Worthington, OH? 2.5 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in Worthington needs
2.5 tons central AC or heat pump, about 29,000 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, about 45% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.
If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 828 square feet in this climate. For a single room, size by the room: 14.5 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at Columbus Ohio State University Airport (3.3 mi away). Jul is the hottest month, averaging a high of 84.3°F and a low of 64°F, with about 17 days a year at 90°F or more. That gives a design temperature of 89°F against 75°F inside.
What it costs to run
About 1,277 kWh a year at SEER2 14.3, or roughly $240 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.
What drives the load in Worthington
Of the 29,000 BTU/hr, 10,080 comes through walls, roof and windows on a 89°F afternoon (35%), 13,000 is sun on the house (45%), 2,120 is four people and their appliances, and 3,800 is moisture the coil has to wring out of Worthington's summer air (13%).
Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,200 BTU/hr before the moisture allowance.
Other house sizes in Worthington
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 15,700 | 1.5 tons | 2 tons |
| 1,500 sq ft | 22,300 | 2 tons | 2.5 tons |
| 2,500 sq ft | 35,600 | 3 tons | 5 tons |
| 3,000 sq ft | 42,300 | 4 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,200 BTU/hr; a 350 sq ft living room needs about 5,100 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,700 BTU/hr.
Month by month in Worthington
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 36.3°F | 0 | 0 |
| Feb | 39.8°F | 0 | 0 |
| Mar | 50.2°F | 2 | 2 |
| Apr | 63.3°F | 10 | 13 |
| May | 73.3°F | 69 | 96 |
| Jun | 81.3°F | 193 | 268 |
| Jul | 84.3°F | 285 | 396 |
| Aug | 83.2°F | 245 | 340 |
| Sep | 77°F | 100 | 139 |
| Oct | 64.7°F | 15 | 20 |
| Nov | 51.4°F | 0 | 0 |
| Dec | 40.4°F | 0 | 0 |
Jul alone uses 31% of the year's cooling energy. The unit runs the equivalent of 630 hours a year at full output.
Worthington against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| Upper Arlington, OH | 5 mi | 89°F | 2.5 tons |
| Powell, OH | 6 mi | 89°F | 2.5 tons |
| Westerville, OH | 6 mi | 89°F | 2.5 tons |
| Dublin, OH | 7 mi | 89°F | 2.5 tons |
| Columbus, OH | 8 mi | 90°F | 2.5 tons |
| Hilliard, OH | 8 mi | 89°F | 2.5 tons |
Of 176 Ohio cities here, Worthington has the 78th highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.
Where Worthington's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is Columbus Ohio State University Airport, 3.3 miles from the center of Worthington at 902 ft above sea level. That is close enough that the station's summers are Worthington's summers.
7 other cities use the same station and get the same climate inputs. The closest to Worthington: Upper Arlington (5 mi away, 3.5 mi from the station), Powell (6 mi away, 6.2 mi from the station), Westerville (6 mi away, 9.3 mi from the station), Dublin (7 mi away, 4.3 mi from the station), Hilliard (8 mi away, 5.2 mi from the station). Worthington sits closer to the station than any of them, so its numbers are the best measured of the group.
The sun over Worthington in late July
At 40.10°N, the noon sun on 21 July stands 70.3° above the horizon over Worthington and the day runs 14 h 26 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.
14,649 people live in Worthington, the 119th largest of the 176 Ohio cities sized on this site. Coordinates used: 40.0969, -83.0202.
Worthington AC sizing questions
What size AC does a 2,000 sq ft house in Worthington, OH need?
About 2.5 tons, for a cooling load of 29,000 BTU/hr on a 89°F design day. That is one ton per 828 square feet in Worthington's climate.
Is 20 BTU per square foot right for Worthington?
The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Columbus Ohio State University Airport. For a single room here, plan on 14.5 BTU/hr per square foot.
What does central AC cost to run in Worthington?
About $240 a year: 1,277 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.