ACSizeCheck

What size AC for Trotwood, OH? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Trotwood needs

2.5 tons central AC or heat pump, about 29,800 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 41% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 805 square feet in this climate. For a single room, size by the room: 14.9 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Dayton International Airport (9.6 mi away). Jul is the hottest month, averaging a high of 85.9°F and a low of 66.1°F, with about 16 days a year at 90°F or more. That gives a design temperature of 90°F against 75°F inside.

What it costs to run

About 1,604 kWh a year at SEER2 14.3, or roughly $302 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Trotwood

Of the 29,800 BTU/hr, 10,800 comes through walls, roof and windows on a 90°F afternoon (36%), 13,000 is sun on the house (44%), 2,120 is four people and their appliances, and 3,900 is moisture the coil has to wring out of Trotwood's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,920 BTU/hr before the moisture allowance.

Other house sizes in Trotwood

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft16,1001.5 tons2 tons
1,500 sq ft23,0002 tons2.5 tons
2,500 sq ft36,7003.5 tons5 tons
3,000 sq ft43,5004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,200 BTU/hr; a 350 sq ft living room needs about 5,200 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,900 BTU/hr.

Month by month in Trotwood

MonthAvg highCooling degree daysAC kWh
Jan37.1°F00
Feb41.2°F00
Mar51.5°F23
Apr64.5°F1521
May74.2°F94131
Jun82.6°F242337
Jul85.9°F341474
Aug84.6°F296411
Sep78.6°F139193
Oct66.2°F2332
Nov52.7°F11
Dec41.5°F00

Jul alone uses 30% of the year's cooling energy. The unit runs the equivalent of 769 hours a year at full output.

Trotwood against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Englewood, OH5 mi90°F2.5 tons
Clayton, OH5 mi90°F2.5 tons
Dayton, OH7 mi90°F2.5 tons
Vandalia, OH9 mi90°F2.5 tons
West Carrollton, OH9 mi90°F2.5 tons
Riverside, OH11 mi90°F2.5 tons

Of 176 Ohio cities here, Trotwood has the 43rd highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.

Where Trotwood's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Dayton International Airport, 9.6 miles from the center of Trotwood at 993 ft above sea level. That is close enough that the station's summers are Trotwood's summers.

9 other cities use the same station and get the same climate inputs. The closest to Trotwood: Englewood (5 mi away, 5.6 mi from the station), Clayton (5 mi away, 6.2 mi from the station), Dayton (7 mi away, 8.5 mi from the station), Vandalia (9 mi away, 2.4 mi from the station), Riverside (11 mi away, 9.9 mi from the station). Trotwood is farther from the station than 7 of them.

The sun over Trotwood in late July

At 39.79°N, the noon sun on 21 July stands 70.6° above the horizon over Trotwood and the day runs 14 h 24 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

23,073 people live in Trotwood, the 74th largest of the 176 Ohio cities sized on this site. Coordinates used: 39.7918, -84.3218.

Trotwood AC sizing questions

What size AC does a 2,000 sq ft house in Trotwood, OH need?

About 2.5 tons, for a cooling load of 29,800 BTU/hr on a 90°F design day. That is one ton per 805 square feet in Trotwood's climate.

Is 20 BTU per square foot right for Trotwood?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Dayton International Airport. For a single room here, plan on 14.9 BTU/hr per square foot.

What does central AC cost to run in Trotwood?

About $302 a year: 1,604 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.