What size AC for Smithfield, NC? 3.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Smithfield needs

3.5 tons central AC or heat pump, about 37,800 BTU/hr of load

Here the 20 BTU per square foot chart lands close: 3.5 tons against a load of 3.1 tons. This is one of the climates the chart was written for.

If a contractor quotes you more than 3.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 635 square feet in this climate. For a single room, size by the room: 18.9 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Smithfield (0.6 mi away). Jul is the hottest month, averaging a high of 91.7°F and a low of 70.8°F, with about 53 days a year at 90°F or more. That gives a design temperature of 97°F against 75°F inside.

What it costs to run

About 2,759 kWh a year at SEER2 14.3, or roughly $412 at North Carolina's average residential rate of 14.94¢ per kWh. Cooling runs 7 months of the year here.

What drives the load in Smithfield

Of the 37,800 BTU/hr, 15,840 comes through walls, roof and windows on a 97°F afternoon (42%), 13,000 is sun on the house (34%), 2,120 is four people and their appliances, and 6,800 is moisture the coil has to wring out of Smithfield's summer air (18%).

Heat through the shell is the biggest share here, so insulation and air sealing cut the size you need more than shading would. Sensible heat totals 30,960 BTU/hr before the moisture allowance.

Other house sizes in Smithfield

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft20,2002 tons2 tons
1,500 sq ft29,0002.5 tons2.5 tons
2,500 sq ft46,6004 tons5 tons
3,000 sq ft55,4005 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,800 BTU/hr; a 350 sq ft living room needs about 6,600 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 11,300 BTU/hr.

Month by month in Smithfield

MonthAvg highCooling degree daysAC kWh
Jan53.6°F12
Feb57°F23
Mar64.5°F1015
Apr74.1°F5378
May81°F173256
Jun88.3°F365539
Jul91.7°F504743
Aug89.3°F433638
Sep83.6°F259381
Oct74.3°F6292
Nov64.4°F710
Dec56.7°F34

Jul alone uses 27% of the year's cooling energy. The unit runs the equivalent of 1,044 hours a year at full output.

Smithfield against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Clayton, NC11 mi94°F3 tons
Wendell, NC19 mi97°F3.5 tons
Garner, NC19 mi97°F3.5 tons
Knightdale, NC20 mi97°F3.5 tons
Zebulon, NC21 mi96°F3.5 tons
Goldsboro, NC24 mi97°F3.5 tons

Of 91 North Carolina cities here, Smithfield has the 25th highest cooling load. The range runs from Boone at 21,700 BTU/hr to Lumberton at 40,200.

Where Smithfield's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Smithfield, 0.6 miles from the center of Smithfield at 150 ft above sea level. That is close enough that the station's summers are Smithfield's summers.

No other city in this set uses Smithfield, so this sizing is Smithfield's alone.

The sun over Smithfield in late July

At 35.52°N, the noon sun on 21 July stands 74.9° above the horizon over Smithfield and the day runs 14 h 03 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

12,806 people live in Smithfield, the 78th largest of the 91 North Carolina cities sized on this site. Coordinates used: 35.5238, -78.3522.

Smithfield AC sizing questions

What size AC does a 2,000 sq ft house in Smithfield, NC need?

About 3.5 tons, for a cooling load of 37,800 BTU/hr on a 97°F design day. That is one ton per 635 square feet in Smithfield's climate.

Is 20 BTU per square foot right for Smithfield?

The chart gives 3.5 tons for 2,000 sq ft, against 3.5 tons sized from NOAA's 1991 to 2020 normals at Smithfield. For a single room here, plan on 18.9 BTU/hr per square foot.

What does central AC cost to run in Smithfield?

About $412 a year: 2,759 kWh at SEER2 14.3 and 14.94¢ per kWh, over 7 cooling months.