What size AC for Sidney, OH? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Sidney needs

2.5 tons central AC or heat pump, about 27,200 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 54% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 882 square feet in this climate. For a single room, size by the room: 13.6 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Sidney 1 S (1.6 mi away). Jul is the hottest month, averaging a high of 84.3°F and a low of 62.1°F, with about 14 days a year at 90°F or more. That gives a design temperature of 89°F against 75°F inside.

What it costs to run

About 1,067 kWh a year at SEER2 14.3, or roughly $201 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Sidney

Of the 27,200 BTU/hr, 10,080 comes through walls, roof and windows on a 89°F afternoon (37%), 13,000 is sun on the house (48%), 2,120 is four people and their appliances, and 2,000 is moisture the coil has to wring out of Sidney's summer air (7%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,200 BTU/hr before the moisture allowance.

Other house sizes in Sidney

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft14,8001.5 tons2 tons
1,500 sq ft21,0002 tons2.5 tons
2,500 sq ft33,4003 tons5 tons
3,000 sq ft39,7003.5 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,000 BTU/hr; a 350 sq ft living room needs about 4,800 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,200 BTU/hr.

Month by month in Sidney

MonthAvg highCooling degree daysAC kWh
Jan34.4°F00
Feb38.5°F00
Mar48.9°F11
Apr62.3°F79
May72.8°F5876
Jun81.2°F179234
Jul84.3°F257336
Aug83°F206269
Sep77.9°F95124
Oct65.2°F1418
Nov51.1°F00
Dec39.6°F00

Jul alone uses 31% of the year's cooling energy. The unit runs the equivalent of 561 hours a year at full output.

Sidney against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Piqua, OH11 mi89°F2.5 tons
Troy, OH17 mi90°F2.5 tons
Bellefontaine, OH22 mi87°F2 tons
Tipp City, OH22 mi90°F2.5 tons
Urbana, OH25 mi89°F2.5 tons
Greenville, OH27 mi89°F2.5 tons

Of 176 Ohio cities here, Sidney has the 113th highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.

Where Sidney's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Sidney 1 S, 1.6 miles from the center of Sidney at 940 ft above sea level. That is close enough that the station's summers are Sidney's summers.

No other city in this set uses Sidney 1 S, so this sizing is Sidney's alone.

The sun over Sidney in late July

At 40.29°N, the noon sun on 21 July stands 70.1° above the horizon over Sidney and the day runs 14 h 27 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

20,392 people live in Sidney, the 84th largest of the 176 Ohio cities sized on this site. Coordinates used: 40.2895, -84.1667.

Sidney AC sizing questions

What size AC does a 2,000 sq ft house in Sidney, OH need?

About 2.5 tons, for a cooling load of 27,200 BTU/hr on a 89°F design day. That is one ton per 882 square feet in Sidney's climate.

Is 20 BTU per square foot right for Sidney?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Sidney 1 S. For a single room here, plan on 13.6 BTU/hr per square foot.

What does central AC cost to run in Sidney?

About $201 a year: 1,067 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.