What size AC for Greenville, OH? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Greenville needs

2.5 tons central AC or heat pump, about 27,200 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 54% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 882 square feet in this climate. For a single room, size by the room: 13.6 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Greenville Wtp (1.5 mi away). Jul is the hottest month, averaging a high of 84.6°F and a low of 63.6°F, with about 12 days a year at 90°F or more. That gives a design temperature of 89°F against 75°F inside.

What it costs to run

About 1,217 kWh a year at SEER2 14.3, or roughly $229 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Greenville

Of the 27,200 BTU/hr, 10,080 comes through walls, roof and windows on a 89°F afternoon (37%), 13,000 is sun on the house (48%), 2,120 is four people and their appliances, and 2,000 is moisture the coil has to wring out of Greenville's summer air (7%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,200 BTU/hr before the moisture allowance.

Other house sizes in Greenville

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft14,8001.5 tons2 tons
1,500 sq ft21,0002 tons2.5 tons
2,500 sq ft33,4003 tons5 tons
3,000 sq ft39,7003.5 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,000 BTU/hr; a 350 sq ft living room needs about 4,800 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,200 BTU/hr.

Month by month in Greenville

MonthAvg highCooling degree daysAC kWh
Jan35.1°F00
Feb39.1°F00
Mar49.6°F12
Apr62.8°F1012
May73.2°F77100
Jun81.6°F209272
Jul84.6°F284371
Aug83.3°F230300
Sep78.1°F106138
Oct65.6°F1621
Nov51.6°F01
Dec39.8°F00

Jul alone uses 30% of the year's cooling energy. The unit runs the equivalent of 639 hours a year at full output.

Greenville against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Piqua, OH20 mi89°F2.5 tons
Troy, OH22 mi90°F2.5 tons
Clayton, OH23 mi90°F2.5 tons
Englewood, OH23 mi90°F2.5 tons
Richmond, IN24 mi89°F2.5 tons
Tipp City, OH25 mi90°F2.5 tons

Of 176 Ohio cities here, Greenville has the 116th highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.

Where Greenville's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Greenville Wtp, 1.5 miles from the center of Greenville at 1,030 ft above sea level. That is close enough that the station's summers are Greenville's summers.

No other city in this set uses Greenville Wtp, so this sizing is Greenville's alone.

The sun over Greenville in late July

At 40.10°N, the noon sun on 21 July stands 70.3° above the horizon over Greenville and the day runs 14 h 26 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

12,701 people live in Greenville, the 147th largest of the 176 Ohio cities sized on this site. Coordinates used: 40.1047, -84.6214.

Greenville AC sizing questions

What size AC does a 2,000 sq ft house in Greenville, OH need?

About 2.5 tons, for a cooling load of 27,200 BTU/hr on a 89°F design day. That is one ton per 882 square feet in Greenville's climate.

Is 20 BTU per square foot right for Greenville?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Greenville Wtp. For a single room here, plan on 13.6 BTU/hr per square foot.

What does central AC cost to run in Greenville?

About $229 a year: 1,217 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.