ACSizeCheck

What size AC for Quincy, IL? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Quincy needs

2.5 tons central AC or heat pump, about 30,600 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 37% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 783 square feet in this climate. For a single room, size by the room: 15.3 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Quincy Regional Airport (9.7 mi away). Jul is the hottest month, averaging a high of 86°F and a low of 66.5°F, with about 24 days a year at 90°F or more. That gives a design temperature of 91°F against 75°F inside.

What it costs to run

About 1,602 kWh a year at SEER2 14.3, or roughly $308 at Illinois's average residential rate of 19.23¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Quincy

Of the 30,600 BTU/hr, 11,520 comes through walls, roof and windows on a 91°F afternoon (38%), 13,000 is sun on the house (42%), 2,120 is four people and their appliances, and 4,000 is moisture the coil has to wring out of Quincy's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 26,640 BTU/hr before the moisture allowance.

Other house sizes in Quincy

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft16,5001.5 tons2 tons
1,500 sq ft23,6002 tons2.5 tons
2,500 sq ft37,7003.5 tons5 tons
3,000 sq ft44,7004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,300 BTU/hr; a 350 sq ft living room needs about 5,400 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,200 BTU/hr.

Month by month in Quincy

MonthAvg highCooling degree daysAC kWh
Jan34.6°F00
Feb39.7°F00
Mar51.7°F23
Apr63.7°F1420
May73.3°F87121
Jun82.4°F245341
Jul86°F350486
Aug84.5°F298414
Sep77.9°F133184
Oct65.3°F2332
Nov51.2°F11
Dec39.3°F00

Jul alone uses 30% of the year's cooling energy. The unit runs the equivalent of 748 hours a year at full output.

Quincy against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Hannibal, MO15 mi91°F2.5 tons
Macomb, IL52 mi91°F2.5 tons
Mexico, MO59 mi93°F3 tons
Burlington, IA62 mi90°F2.5 tons
Jacksonville, IL62 mi92°F3 tons
Kirksville, MO66 mi91°F2.5 tons

Of 225 Illinois cities here, Quincy has the 33rd highest cooling load. The range runs from Fox Lake at 24,900 BTU/hr to Granite City at 36,000.

Where Quincy's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Quincy Regional Airport, 9.7 miles from the center of Quincy at 760 ft above sea level. That is close enough that the station's summers are Quincy's summers.

No other city in this set uses Quincy Regional Airport, so this sizing is Quincy's alone.

The sun over Quincy in late July

At 39.93°N, the noon sun on 21 July stands 70.5° above the horizon over Quincy and the day runs 14 h 25 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

38,786 people live in Quincy, the 44th largest of the 225 Illinois cities sized on this site. Coordinates used: 39.9337, -91.3793.

Quincy AC sizing questions

What size AC does a 2,000 sq ft house in Quincy, IL need?

About 2.5 tons, for a cooling load of 30,600 BTU/hr on a 91°F design day. That is one ton per 783 square feet in Quincy's climate.

Is 20 BTU per square foot right for Quincy?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Quincy Regional Airport. For a single room here, plan on 15.3 BTU/hr per square foot.

What does central AC cost to run in Quincy?

About $308 a year: 1,602 kWh at SEER2 14.3 and 19.23¢ per kWh, over 5 cooling months.