What size AC for New York, NY? 2.5 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in New York needs
2.5 tons central AC or heat pump, about 30,700 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, about 37% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.
If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 781 square feet in this climate. For a single room, size by the room: 15.4 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at NY City Central Park (8.2 mi away). Jul is the hottest month, averaging a high of 84.9°F and a low of 70.1°F, with about 17 days a year at 90°F or more. That gives a design temperature of 89°F against 75°F inside.
What it costs to run
About 1,801 kWh a year at SEER2 14.3, or roughly $527 at New York's average residential rate of 29.26¢ per kWh. Cooling runs 5 months of the year here.
What drives the load in New York
Of the 30,700 BTU/hr, 10,080 comes through walls, roof and windows on a 89°F afternoon (33%), 13,000 is sun on the house (42%), 2,120 is four people and their appliances, and 5,500 is moisture the coil has to wring out of New York's summer air (18%).
Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,200 BTU/hr before the moisture allowance.
Other house sizes in New York
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 16,700 | 1.5 tons | 2 tons |
| 1,500 sq ft | 23,700 | 2 tons | 2.5 tons |
| 2,500 sq ft | 37,800 | 3.5 tons | 5 tons |
| 3,000 sq ft | 44,800 | 4 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,300 BTU/hr; a 350 sq ft living room needs about 5,400 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,200 BTU/hr.
Month by month in New York
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 39.5°F | 0 | 0 |
| Feb | 42.2°F | 0 | 0 |
| Mar | 49.9°F | 1 | 2 |
| Apr | 61.8°F | 14 | 20 |
| May | 71.4°F | 66 | 98 |
| Jun | 79.7°F | 226 | 333 |
| Jul | 84.9°F | 388 | 571 |
| Aug | 83.3°F | 345 | 508 |
| Sep | 76.2°F | 159 | 235 |
| Oct | 64.5°F | 22 | 32 |
| Nov | 54°F | 1 | 1 |
| Dec | 44.3°F | 0 | 0 |
Jul alone uses 32% of the year's cooling energy. The unit runs the equivalent of 838 hours a year at full output.
New York against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| Hoboken, NJ | 7 mi | 89°F | 2.5 tons |
| Jersey City, NJ | 7 mi | 92°F | 3 tons |
| Union City, NJ | 9 mi | 89°F | 2.5 tons |
| Bayonne, NJ | 9 mi | 92°F | 3 tons |
| West New York, NJ | 9 mi | 89°F | 2.5 tons |
| Guttenberg, NJ | 10 mi | 89°F | 2.5 tons |
Of 90 New York cities here, New York has the 7th highest cooling load. The range runs from Gloversville at 20,200 BTU/hr to Spring Valley at 33,400.
Where New York's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is NY City Central Park, 8.2 miles from the center of New York at 140 ft above sea level. That is close enough that the station's summers are New York's summers.
8 other cities use the same station and get the same climate inputs. The closest to New York: Hoboken (7 mi away, 3.9 mi from the station), Union City (9 mi away, 3.4 mi from the station), West New York (9 mi away, 2.2 mi from the station), Guttenberg (10 mi away, 2.1 mi from the station), Secaucus (11 mi away, 5.2 mi from the station). New York is farther from the station than 8 of them.
The sun over New York in late July
At 40.66°N, the noon sun on 21 July stands 69.7° above the horizon over New York and the day runs 14 h 29 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.
8,478,072 people live in New York, the largest of the 90 New York cities sized on this site. Coordinates used: 40.6627, -73.9387.
New York AC sizing questions
What size AC does a 2,000 sq ft house in New York, NY need?
About 2.5 tons, for a cooling load of 30,700 BTU/hr on a 89°F design day. That is one ton per 781 square feet in New York's climate.
Is 20 BTU per square foot right for New York?
The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at NY City Central Park. For a single room here, plan on 15.4 BTU/hr per square foot.
What does central AC cost to run in New York?
About $527 a year: 1,801 kWh at SEER2 14.3 and 29.26¢ per kWh, over 5 cooling months.