ACSizeCheck

What size AC for Columbus, GA? 4 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Columbus needs

4 tons central AC or heat pump, about 43,100 BTU/hr of load

Here the 20 BTU per square foot chart lands close: 3.5 tons against a load of 3.6 tons. This is one of the climates the chart was written for.

If a contractor quotes you more than 4 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 557 square feet in this climate. For a single room, size by the room: 21.5 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Columbus Metro Airport (3.9 mi away). Jul is the hottest month, averaging a high of 92.9°F and a low of 73.5°F, with about 81 days a year at 90°F or more. That gives a design temperature of 100°F against 75°F inside.

What it costs to run

About 3,980 kWh a year at SEER2 14.3, or roughly $616 at Georgia's average residential rate of 15.48¢ per kWh. Cooling runs 7 months of the year here.

What drives the load in Columbus

Of the 43,100 BTU/hr, 18,000 comes through walls, roof and windows on a 100°F afternoon (42%), 13,000 is sun on the house (30%), 2,120 is four people and their appliances, and 9,900 is moisture the coil has to wring out of Columbus's summer air (23%).

Heat through the shell is the biggest share here, so insulation and air sealing cut the size you need more than shading would. Sensible heat totals 33,120 BTU/hr before the moisture allowance.

Other house sizes in Columbus

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft22,9002 tons2 tons
1,500 sq ft33,0003 tons2.5 tons
2,500 sq ft53,1005 tons5 tons
3,000 sq ft63,2005 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 3,200 BTU/hr; a 350 sq ft living room needs about 7,500 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 12,900 BTU/hr.

Month by month in Columbus

MonthAvg highCooling degree daysAC kWh
Jan58.7°F24
Feb63.2°F710
Mar70.4°F3148
Apr77.7°F96151
May85.1°F289453
Jun90.2°F461723
Jul92.9°F564886
Aug91.8°F539847
Sep87.3°F379595
Oct78.3°F138217
Nov68.4°F2337
Dec60.6°F58

Jul alone uses 22% of the year's cooling energy. The unit runs the equivalent of 1,322 hours a year at full output.

Columbus against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Phenix City, AL10 mi100°F4 tons
Valley, AL27 mi96°F3.5 tons
Opelika, AL31 mi95°F3 tons
Auburn, AL36 mi95°F3 tons
LaGrange, GA37 mi97°F3.5 tons
Eufaula, AL45 mi102°F4 tons

Of 101 Georgia cities here, Columbus has the 2nd highest cooling load. The range runs from Cumming at 33,100 BTU/hr to Albany at 44,000.

Where Columbus's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Columbus Metro Airport, 3.9 miles from the center of Columbus at 394 ft above sea level. That is close enough that the station's summers are Columbus's summers.

1 other city uses the same station and get the same climate inputs. The closest to Columbus: Phenix City (10 mi away, 6.7 mi from the station). Columbus sits closer to the station than any of them, so its numbers are the best measured of the group.

The sun over Columbus in late July

At 32.51°N, the noon sun on 21 July stands 77.9° above the horizon over Columbus and the day runs 13 h 50 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

201,830 people live in Columbus, the 2nd largest of the 101 Georgia cities sized on this site. Coordinates used: 32.5102, -84.8749.

Columbus AC sizing questions

What size AC does a 2,000 sq ft house in Columbus, GA need?

About 4 tons, for a cooling load of 43,100 BTU/hr on a 100°F design day. That is one ton per 557 square feet in Columbus's climate.

Is 20 BTU per square foot right for Columbus?

The chart gives 3.5 tons for 2,000 sq ft, against 4 tons sized from NOAA's 1991 to 2020 normals at Columbus Metro Airport. For a single room here, plan on 21.5 BTU/hr per square foot.

What does central AC cost to run in Columbus?

About $616 a year: 3,980 kWh at SEER2 14.3 and 15.48¢ per kWh, over 7 cooling months.