ACSizeCheck

What size AC for Redmond, OR? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Redmond needs

2.5 tons central AC or heat pump, about 29,200 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 44% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 822 square feet in this climate. For a single room, size by the room: 14.6 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Redmond Airport (2.1 mi away). Jul is the hottest month, averaging a high of 87.5°F and a low of 48.5°F, with about 32 days a year at 90°F or more. That gives a design temperature of 93°F against 75°F inside.

What it costs to run

About 399 kWh a year at SEER2 14.3, or roughly $62 at Oregon's average residential rate of 15.46¢ per kWh. Cooling runs 2 months of the year here.

What drives the load in Redmond

Of the 29,200 BTU/hr, 12,960 comes through walls, roof and windows on a 93°F afternoon (44%), 13,000 is sun on the house (45%), 2,120 is four people and their appliances, and 1,100 is moisture the coil has to wring out of Redmond's summer air (4%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 28,080 BTU/hr before the moisture allowance.

Other house sizes in Redmond

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft15,7001.5 tons2 tons
1,500 sq ft22,5002 tons2.5 tons
2,500 sq ft36,0003 tons5 tons
3,000 sq ft42,7004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,200 BTU/hr; a 350 sq ft living room needs about 5,100 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,800 BTU/hr.

Month by month in Redmond

MonthAvg highCooling degree daysAC kWh
Jan44.2°F00
Feb48°F00
Mar54.9°F00
Apr60.2°F00
May69.1°F79
Jun77.2°F3341
Jul87.5°F136171
Aug86.5°F110138
Sep78.6°F3038
Oct64.5°F11
Nov50.8°F00
Dec42.3°F00

Jul alone uses 43% of the year's cooling energy. The unit runs the equivalent of 195 hours a year at full output.

Redmond against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Bend, OR15 mi93°F2.5 tons
Prineville, OR16 mi93°F2.5 tons
Sweet Home, OR76 mi87°F2 tons
Lebanon, OR87 mi91°F2.5 tons
Springfield, OR90 mi89°F2.5 tons
Molalla, OR92 mi88°F2 tons

Of 57 Oregon cities here, Redmond has the 9th highest cooling load. The range runs from North Bend at 15,700 BTU/hr to Ontario at 36,500.

Where Redmond's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Redmond Airport, 2.1 miles from the center of Redmond at 3,049 ft above sea level. That is close enough that the station's summers are Redmond's summers.

2 other cities use the same station and get the same climate inputs. The closest to Redmond: Bend (15 mi away, 16.1 mi from the station), Prineville (16 mi away, 14.2 mi from the station). Redmond sits closer to the station than any of them, so its numbers are the best measured of the group.

The sun over Redmond in late July

At 44.26°N, the noon sun on 21 July stands 66.1° above the horizon over Redmond and the day runs 14 h 50 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Long days mean the house keeps gaining heat into the evening, well after the outdoor peak.

37,626 people live in Redmond, the 17th largest of the 57 Oregon cities sized on this site. Coordinates used: 44.2607, -121.1824.

Redmond AC sizing questions

What size AC does a 2,000 sq ft house in Redmond, OR need?

About 2.5 tons, for a cooling load of 29,200 BTU/hr on a 93°F design day. That is one ton per 822 square feet in Redmond's climate.

Is 20 BTU per square foot right for Redmond?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Redmond Airport. For a single room here, plan on 14.6 BTU/hr per square foot.

What does central AC cost to run in Redmond?

About $62 a year: 399 kWh at SEER2 14.3 and 15.46¢ per kWh, over 2 cooling months.