ACSizeCheck

What size AC for Reading, PA? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Reading needs

2.5 tons central AC or heat pump, about 30,600 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 37% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 783 square feet in this climate. For a single room, size by the room: 15.3 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Reading Regional Airport (2.9 mi away). Jul is the hottest month, averaging a high of 86.5°F and a low of 65.8°F, with about 24 days a year at 90°F or more. That gives a design temperature of 91°F against 75°F inside.

What it costs to run

About 1,467 kWh a year at SEER2 14.3, or roughly $310 at Pennsylvania's average residential rate of 21.13¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Reading

Of the 30,600 BTU/hr, 11,520 comes through walls, roof and windows on a 91°F afternoon (38%), 13,000 is sun on the house (42%), 2,120 is four people and their appliances, and 4,000 is moisture the coil has to wring out of Reading's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 26,640 BTU/hr before the moisture allowance.

Other house sizes in Reading

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft16,5001.5 tons2 tons
1,500 sq ft23,6002 tons2.5 tons
2,500 sq ft37,7003.5 tons5 tons
3,000 sq ft44,7004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,300 BTU/hr; a 350 sq ft living room needs about 5,400 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,200 BTU/hr.

Month by month in Reading

MonthAvg highCooling degree daysAC kWh
Jan38.6°F00
Feb41.9°F00
Mar51°F01
Apr63.4°F1116
May73.5°F6489
Jun82°F215298
Jul86.5°F346481
Aug84.4°F289402
Sep77.1°F115160
Oct65.4°F1521
Nov53.8°F00
Dec43.4°F00

Jul alone uses 33% of the year's cooling energy. The unit runs the equivalent of 685 hours a year at full output.

Reading against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Wyomissing, PA2 mi91°F2.5 tons
Pottstown, PA16 mi88°F2.5 tons
Ephrata, PA17 mi91°F2.5 tons
Coatesville, PA25 mi88°F2.5 tons
Phoenixville, PA26 mi88°F2.5 tons
Lebanon, PA26 mi91°F2.5 tons

Of 68 Pennsylvania cities here, Reading has the 11th highest cooling load. The range runs from St. Marys at 21,700 BTU/hr to Philadelphia at 34,300.

Where Reading's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Reading Regional Airport, 2.9 miles from the center of Reading at 332 ft above sea level. That is close enough that the station's summers are Reading's summers.

2 other cities use the same station and get the same climate inputs. The closest to Reading: Wyomissing (2 mi away, 2.7 mi from the station), Pottsville (28 mi away, 24.9 mi from the station). Reading is farther from the station than 1 of them.

The sun over Reading in late July

At 40.34°N, the noon sun on 21 July stands 70.1° above the horizon over Reading and the day runs 14 h 27 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

96,000 people live in Reading, the 4th largest of the 68 Pennsylvania cities sized on this site. Coordinates used: 40.3392, -75.9263.

Reading AC sizing questions

What size AC does a 2,000 sq ft house in Reading, PA need?

About 2.5 tons, for a cooling load of 30,600 BTU/hr on a 91°F design day. That is one ton per 783 square feet in Reading's climate.

Is 20 BTU per square foot right for Reading?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Reading Regional Airport. For a single room here, plan on 15.3 BTU/hr per square foot.

What does central AC cost to run in Reading?

About $310 a year: 1,467 kWh at SEER2 14.3 and 21.13¢ per kWh, over 5 cooling months.