What size AC for North Olmsted, OH? 2.5 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in North Olmsted needs
2.5 tons central AC or heat pump, about 28,200 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, about 49% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.
If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 853 square feet in this climate. For a single room, size by the room: 14.1 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at Cleveland (3.1 mi away). Jul is the hottest month, averaging a high of 83.7°F and a low of 65.3°F, with about 12 days a year at 90°F or more. That gives a design temperature of 88°F against 75°F inside.
What it costs to run
About 1,316 kWh a year at SEER2 14.3, or roughly $248 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.
What drives the load in North Olmsted
Of the 28,200 BTU/hr, 9,360 comes through walls, roof and windows on a 88°F afternoon (33%), 13,000 is sun on the house (46%), 2,120 is four people and their appliances, and 3,700 is moisture the coil has to wring out of North Olmsted's summer air (13%).
Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 24,480 BTU/hr before the moisture allowance.
Other house sizes in North Olmsted
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 15,300 | 1.5 tons | 2 tons |
| 1,500 sq ft | 21,700 | 2 tons | 2.5 tons |
| 2,500 sq ft | 34,600 | 3 tons | 5 tons |
| 3,000 sq ft | 41,000 | 3.5 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,100 BTU/hr; a 350 sq ft living room needs about 4,900 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,500 BTU/hr.
Month by month in North Olmsted
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 35.8°F | 0 | 0 |
| Feb | 38.5°F | 0 | 0 |
| Mar | 47.1°F | 2 | 3 |
| Apr | 60.1°F | 10 | 14 |
| May | 71.1°F | 66 | 91 |
| Jun | 79.8°F | 193 | 268 |
| Jul | 83.7°F | 296 | 412 |
| Aug | 82°F | 251 | 349 |
| Sep | 75.6°F | 110 | 153 |
| Oct | 63.7°F | 18 | 26 |
| Nov | 51.3°F | 1 | 1 |
| Dec | 40.4°F | 0 | 0 |
Jul alone uses 31% of the year's cooling energy. The unit runs the equivalent of 669 hours a year at full output.
North Olmsted against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| Westlake, OH | 2 mi | 88°F | 2.5 tons |
| Fairview Park, OH | 4 mi | 88°F | 2.5 tons |
| Berea, OH | 4 mi | 88°F | 2.5 tons |
| Avon, OH | 5 mi | 88°F | 2.5 tons |
| Bay Village, OH | 5 mi | 88°F | 2.5 tons |
| Brook Park, OH | 5 mi | 88°F | 2.5 tons |
Of 176 Ohio cities here, North Olmsted has the 88th highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.
Where North Olmsted's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is Cleveland, 3.1 miles from the center of North Olmsted at 860 ft above sea level. That is close enough that the station's summers are North Olmsted's summers.
19 other cities use the same station and get the same climate inputs. The closest to North Olmsted: Westlake (2 mi away, 4.4 mi from the station), Fairview Park (4 mi away, 2 mi from the station), Berea (4 mi away, 3 mi from the station), Avon (5 mi away, 7.8 mi from the station), Bay Village (5 mi away, 6.3 mi from the station). North Olmsted is farther from the station than 3 of them.
The sun over North Olmsted in late July
At 41.41°N, the noon sun on 21 July stands 69.0° above the horizon over North Olmsted and the day runs 14 h 33 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Long days mean the house keeps gaining heat into the evening, well after the outdoor peak.
31,690 people live in North Olmsted, the 47th largest of the 176 Ohio cities sized on this site. Coordinates used: 41.4149, -81.9191.
North Olmsted AC sizing questions
What size AC does a 2,000 sq ft house in North Olmsted, OH need?
About 2.5 tons, for a cooling load of 28,200 BTU/hr on a 88°F design day. That is one ton per 853 square feet in North Olmsted's climate.
Is 20 BTU per square foot right for North Olmsted?
The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Cleveland. For a single room here, plan on 14.1 BTU/hr per square foot.
What does central AC cost to run in North Olmsted?
About $248 a year: 1,316 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.