What size AC for New Albany, OH? 2.5 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in New Albany needs
2.5 tons central AC or heat pump, about 29,800 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, about 41% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.
If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 805 square feet in this climate. For a single room, size by the room: 14.9 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at John Glenn International Airport (8.7 mi away). Jul is the hottest month, averaging a high of 85.4°F and a low of 65.4°F, with about 21 days a year at 90°F or more. That gives a design temperature of 90°F against 75°F inside.
What it costs to run
About 1,484 kWh a year at SEER2 14.3, or roughly $279 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 5 months of the year here.
What drives the load in New Albany
Of the 29,800 BTU/hr, 10,800 comes through walls, roof and windows on a 90°F afternoon (36%), 13,000 is sun on the house (44%), 2,120 is four people and their appliances, and 3,900 is moisture the coil has to wring out of New Albany's summer air (13%).
Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 25,920 BTU/hr before the moisture allowance.
Other house sizes in New Albany
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 16,100 | 1.5 tons | 2 tons |
| 1,500 sq ft | 23,000 | 2 tons | 2.5 tons |
| 2,500 sq ft | 36,700 | 3.5 tons | 5 tons |
| 3,000 sq ft | 43,500 | 4 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,200 BTU/hr; a 350 sq ft living room needs about 5,200 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,900 BTU/hr.
Month by month in New Albany
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 37.1°F | 0 | 0 |
| Feb | 40.8°F | 0 | 0 |
| Mar | 51.1°F | 2 | 2 |
| Apr | 64.1°F | 12 | 17 |
| May | 74.1°F | 84 | 116 |
| Jun | 82.2°F | 223 | 310 |
| Jul | 85.4°F | 323 | 449 |
| Aug | 84.1°F | 282 | 391 |
| Sep | 77.8°F | 125 | 174 |
| Oct | 65.5°F | 18 | 25 |
| Nov | 52.3°F | 0 | 0 |
| Dec | 41.5°F | 0 | 0 |
Jul alone uses 30% of the year's cooling energy. The unit runs the equivalent of 712 hours a year at full output.
New Albany against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| Pataskala, OH | 6 mi | 90°F | 2.5 tons |
| Gahanna, OH | 7 mi | 90°F | 2.5 tons |
| Westerville, OH | 8 mi | 89°F | 2.5 tons |
| Reynoldsburg, OH | 9 mi | 90°F | 2.5 tons |
| Whitehall, OH | 10 mi | 90°F | 2.5 tons |
| Bexley, OH | 12 mi | 90°F | 2.5 tons |
Of 176 Ohio cities here, New Albany has the 62nd highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.
Where New Albany's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is John Glenn International Airport, 8.7 miles from the center of New Albany at 810 ft above sea level. That is close enough that the station's summers are New Albany's summers.
9 other cities use the same station and get the same climate inputs. The closest to New Albany: Pataskala (6 mi away, 8.6 mi from the station), Gahanna (7 mi away, 3.2 mi from the station), Reynoldsburg (9 mi away, 5.1 mi from the station), Whitehall (10 mi away, 1.5 mi from the station), Bexley (12 mi away, 3.5 mi from the station). New Albany is farther from the station than 6 of them.
The sun over New Albany in late July
At 40.09°N, the noon sun on 21 July stands 70.3° above the horizon over New Albany and the day runs 14 h 26 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.
11,604 people live in New Albany, the 154th largest of the 176 Ohio cities sized on this site. Coordinates used: 40.0900, -82.7763.
New Albany AC sizing questions
What size AC does a 2,000 sq ft house in New Albany, OH need?
About 2.5 tons, for a cooling load of 29,800 BTU/hr on a 90°F design day. That is one ton per 805 square feet in New Albany's climate.
Is 20 BTU per square foot right for New Albany?
The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at John Glenn International Airport. For a single room here, plan on 14.9 BTU/hr per square foot.
What does central AC cost to run in New Albany?
About $279 a year: 1,484 kWh at SEER2 14.3 and 18.81¢ per kWh, over 5 cooling months.