ACSizeCheck

What size AC for Manhattan Beach, CA? 2 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Manhattan Beach needs

2 tons central AC or heat pump, about 22,400 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 88% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 1,074 square feet in this climate. For a single room, size by the room: 11.2 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Los Angeles International Airport (3.2 mi away). Aug is the hottest month, averaging a high of 76.7°F and a low of 64.8°F, with about 5 days a year at 90°F or more. That gives a design temperature of 81°F against 75°F inside.

What it costs to run

About 1,001 kWh a year at SEER2 14.3, or roughly $326 at California's average residential rate of 32.58¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Manhattan Beach

Of the 22,400 BTU/hr, 4,320 comes through walls, roof and windows on a 81°F afternoon (19%), 13,000 is sun on the house (58%), 2,120 is four people and their appliances, and 2,900 is moisture the coil has to wring out of Manhattan Beach's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 19,440 BTU/hr before the moisture allowance.

Other house sizes in Manhattan Beach

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft12,4001.5 tons2 tons
1,500 sq ft17,4001.5 tons2.5 tons
2,500 sq ft27,3002.5 tons5 tons
3,000 sq ft32,3003 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 1,700 BTU/hr; a 350 sq ft living room needs about 3,900 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 6,700 BTU/hr.

Month by month in Manhattan Beach

MonthAvg highCooling degree daysAC kWh
Jan66.3°F68
Feb65.6°F710
Mar66.1°F912
Apr68.1°F1724
May69.5°F2534
Jun72°F5779
Jul75.1°F143198
Aug76.7°F179249
Sep76.5°F155216
Oct74.4°F91127
Nov70.9°F3042
Dec66.1°F34

Aug alone uses 25% of the year's cooling energy. The unit runs the equivalent of 640 hours a year at full output.

Manhattan Beach against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
El Segundo, CA1 mi81°F2 tons
Hermosa Beach, CA2 mi81°F2 tons
Redondo Beach, CA4 mi82°F2 tons
Lawndale, CA4 mi83°F2 tons
Hawthorne, CA4 mi83°F2 tons
Inglewood, CA6 mi83°F2 tons

Of 376 California cities here, Manhattan Beach has the 291st highest cooling load. The range runs from Corte Madera at 15,700 BTU/hr to Palm Desert at 59,000.

Where Manhattan Beach's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Los Angeles International Airport, 3.2 miles from the center of Manhattan Beach at 97 ft above sea level. That is close enough that the station's summers are Manhattan Beach's summers.

2 other cities use the same station and get the same climate inputs. The closest to Manhattan Beach: El Segundo (1 mi away, 2.9 mi from the station), Hermosa Beach (2 mi away, 4.8 mi from the station). Manhattan Beach is farther from the station than 1 of them.

The sun over Manhattan Beach in late July

At 33.90°N, the noon sun on 21 July stands 76.5° above the horizon over Manhattan Beach and the day runs 13 h 56 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

33,453 people live in Manhattan Beach, the 225th largest of the 376 California cities sized on this site. Coordinates used: 33.9009, -118.4207.

Manhattan Beach AC sizing questions

What size AC does a 2,000 sq ft house in Manhattan Beach, CA need?

About 2 tons, for a cooling load of 22,400 BTU/hr on a 81°F design day. That is one ton per 1,074 square feet in Manhattan Beach's climate.

Is 20 BTU per square foot right for Manhattan Beach?

The chart gives 3.5 tons for 2,000 sq ft, against 2 tons sized from NOAA's 1991 to 2020 normals at Los Angeles International Airport. For a single room here, plan on 11.2 BTU/hr per square foot.

What does central AC cost to run in Manhattan Beach?

About $326 a year: 1,001 kWh at SEER2 14.3 and 32.58¢ per kWh, over 5 cooling months.