What size AC for Harlingen, TX? 4 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in Harlingen needs
4 tons central AC or heat pump, about 47,700 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, which falls short here. On a design day the unit runs flat out and the house still drifts above 75°F by late afternoon.
If a contractor quotes you more than 4 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 503 square feet in this climate. For a single room, size by the room: 23.9 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at Harlingen Rio Grande Vly International (3.7 mi away). Aug is the hottest month, averaging a high of 97.2°F and a low of 75.3°F, with about 163 days a year at 90°F or more. That gives a design temperature of 105°F against 75°F inside.
What it costs to run
About 6,629 kWh a year at SEER2 14.3, or roughly $1,063 at Texas's average residential rate of 16.03¢ per kWh. Cooling runs 12 months of the year here.
What drives the load in Harlingen
Of the 47,700 BTU/hr, 21,600 comes through walls, roof and windows on a 105°F afternoon (45%), 13,000 is sun on the house (27%), 2,120 is four people and their appliances, and 11,000 is moisture the coil has to wring out of Harlingen's summer air (23%).
Heat through the shell is the biggest share here, so insulation and air sealing cut the size you need more than shading would. Sensible heat totals 36,720 BTU/hr before the moisture allowance.
Other house sizes in Harlingen
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 25,200 | 2 tons | 2 tons |
| 1,500 sq ft | 36,500 | 3 tons | 2.5 tons |
| 2,500 sq ft | 59,000 | 5 tons | 5 tons |
| 3,000 sq ft | 70,200 | 5 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 3,600 BTU/hr; a 350 sq ft living room needs about 8,400 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 14,300 BTU/hr.
Month by month in Harlingen
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 71.7°F | 59 | 92 |
| Feb | 75.9°F | 102 | 160 |
| Mar | 81°F | 201 | 315 |
| Apr | 86.5°F | 332 | 522 |
| May | 91.4°F | 502 | 789 |
| Jun | 95°F | 594 | 933 |
| Jul | 96.2°F | 643 | 1,011 |
| Aug | 97.2°F | 659 | 1,034 |
| Sep | 92.2°F | 521 | 818 |
| Oct | 87.6°F | 364 | 572 |
| Nov | 79.3°F | 162 | 255 |
| Dec | 73.2°F | 82 | 128 |
Aug alone uses 16% of the year's cooling energy. The unit runs the equivalent of 1,986 hours a year at full output.
Harlingen against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| San Benito, TX | 5 mi | 105°F | 4 tons |
| Mercedes, TX | 14 mi | 105°F | 4 tons |
| Weslaco, TX | 18 mi | 108°F | 4 tons |
| Brownsville, TX | 19 mi | 104°F | 4 tons |
| Raymondville, TX | 20 mi | 106°F | 4 tons |
| Donna, TX | 21 mi | 108°F | 4 tons |
Of 252 Texas cities here, Harlingen has the 40th highest cooling load. The range runs from Levelland at 37,300 BTU/hr to Laredo at 51,500.
Where Harlingen's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is Harlingen Rio Grande Vly International, 3.7 miles from the center of Harlingen at 31 ft above sea level. That is close enough that the station's summers are Harlingen's summers.
2 other cities use the same station and get the same climate inputs. The closest to Harlingen: San Benito (5 mi away, 7 mi from the station), Mercedes (14 mi away, 16.8 mi from the station). Harlingen sits closer to the station than any of them, so its numbers are the best measured of the group.
The sun over Harlingen in late July
At 26.19°N, the noon sun on 21 July stands 84.2° above the horizon over Harlingen and the day runs 13 h 24 min from sunrise to sunset. With the sun that close to overhead, the roof takes most of the heat at midday and the west wall takes the rest after 3 pm. Shorter days give the house a longer night to shed the day's heat.
72,234 people live in Harlingen, the 57th largest of the 252 Texas cities sized on this site. Coordinates used: 26.1912, -97.6974.
Harlingen AC sizing questions
What size AC does a 2,000 sq ft house in Harlingen, TX need?
About 4 tons, for a cooling load of 47,700 BTU/hr on a 105°F design day. That is one ton per 503 square feet in Harlingen's climate.
Is 20 BTU per square foot right for Harlingen?
The chart gives 3.5 tons for 2,000 sq ft, against 4 tons sized from NOAA's 1991 to 2020 normals at Harlingen Rio Grande Vly International. For a single room here, plan on 23.9 BTU/hr per square foot.
What does central AC cost to run in Harlingen?
About $1,063 a year: 6,629 kWh at SEER2 14.3 and 16.03¢ per kWh, over 12 cooling months.