ACSizeCheck

What size AC for Fremont, NE? 3 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Fremont needs

3 tons central AC or heat pump, about 31,500 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 33% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 3 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 763 square feet in this climate. For a single room, size by the room: 15.7 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Fremont (1.2 mi away). Jul is the hottest month, averaging a high of 86.7°F and a low of 65.1°F, with about 34 days a year at 90°F or more. That gives a design temperature of 92°F against 75°F inside.

What it costs to run

About 1,454 kWh a year at SEER2 14.3, or roughly $188 at Nebraska's average residential rate of 12.92¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Fremont

Of the 31,500 BTU/hr, 12,240 comes through walls, roof and windows on a 92°F afternoon (39%), 13,000 is sun on the house (41%), 2,120 is four people and their appliances, and 4,100 is moisture the coil has to wring out of Fremont's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 27,360 BTU/hr before the moisture allowance.

Other house sizes in Fremont

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft17,0001.5 tons2 tons
1,500 sq ft24,2002 tons2.5 tons
2,500 sq ft38,7003.5 tons5 tons
3,000 sq ft46,0004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,400 BTU/hr; a 350 sq ft living room needs about 5,500 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,400 BTU/hr.

Month by month in Fremont

MonthAvg highCooling degree daysAC kWh
Jan32.4°F00
Feb37.1°F00
Mar50.1°F11
Apr62.8°F912
May73.4°F7097
Jun83.3°F231321
Jul86.7°F340473
Aug84.5°F270375
Sep78.1°F112156
Oct65°F1420
Nov49.5°F00
Dec36.3°F00

Jul alone uses 33% of the year's cooling energy. The unit runs the equivalent of 661 hours a year at full output.

Fremont against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Omaha, NE26 mi90°F2.5 tons
La Vista, NE28 mi90°F2.5 tons
Papillion, NE29 mi90°F2.5 tons
Bellevue, NE35 mi93°F3 tons
Council Bluffs, IA36 mi93°F3 tons
Lincoln, NE45 mi95°F3 tons

Of 16 Nebraska cities here, Fremont has the 8th highest cooling load. The range runs from South Sioux City at 28,000 BTU/hr to Bellevue at 34,300.

Where Fremont's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Fremont, 1.2 miles from the center of Fremont at 1,180 ft above sea level. That is close enough that the station's summers are Fremont's summers.

No other city in this set uses Fremont, so this sizing is Fremont's alone.

The sun over Fremont in late July

At 41.44°N, the noon sun on 21 July stands 69.0° above the horizon over Fremont and the day runs 14 h 33 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Long days mean the house keeps gaining heat into the evening, well after the outdoor peak.

28,190 people live in Fremont, the 6th largest of the 16 Nebraska cities sized on this site. Coordinates used: 41.4398, -96.4870.

Fremont AC sizing questions

What size AC does a 2,000 sq ft house in Fremont, NE need?

About 3 tons, for a cooling load of 31,500 BTU/hr on a 92°F design day. That is one ton per 763 square feet in Fremont's climate.

Is 20 BTU per square foot right for Fremont?

The chart gives 3.5 tons for 2,000 sq ft, against 3 tons sized from NOAA's 1991 to 2020 normals at Fremont. For a single room here, plan on 15.7 BTU/hr per square foot.

What does central AC cost to run in Fremont?

About $188 a year: 1,454 kWh at SEER2 14.3 and 12.92¢ per kWh, over 5 cooling months.