What size AC for Fairview, TN? 3 tons for 2,000 sq ft
What size AC a 2,000 sq ft house in Fairview needs
3 tons central AC or heat pump, about 35,100 BTU/hr of load
The 20 BTU per square foot chart would put in 3.5 tons, about 20% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.
If a contractor quotes you more than 3 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 683 square feet in this climate. For a single room, size by the room: 17.6 BTU/hr per square foot.
The climate it is sized for
Climate from NOAA's 1991 to 2020 normals at Fairview Bowie Nat Ctr (1.1 mi away). Jul is the hottest month, averaging a high of 88.6°F and a low of 68.4°F, with about 42 days a year at 90°F or more. That gives a design temperature of 94°F against 75°F inside.
What it costs to run
About 2,278 kWh a year at SEER2 14.3, or roughly $314 at Tennessee's average residential rate of 13.8¢ per kWh. Cooling runs 5 months of the year here.
What drives the load in Fairview
Of the 35,100 BTU/hr, 13,680 comes through walls, roof and windows on a 94°F afternoon (39%), 13,000 is sun on the house (37%), 2,120 is four people and their appliances, and 6,300 is moisture the coil has to wring out of Fairview's summer air (18%).
Heat through the shell is the biggest share here, so insulation and air sealing cut the size you need more than shading would. Sensible heat totals 28,800 BTU/hr before the moisture allowance.
Other house sizes in Fairview
| House | Load, BTU/hr | Size | 20 BTU/ft² chart |
|---|---|---|---|
| 1,000 sq ft | 18,900 | 1.5 tons | 2 tons |
| 1,500 sq ft | 27,000 | 2.5 tons | 2.5 tons |
| 2,500 sq ft | 43,300 | 4 tons | 5 tons |
| 3,000 sq ft | 51,400 | 4 tons | 5 tons |
Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,600 BTU/hr; a 350 sq ft living room needs about 6,200 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 10,600 BTU/hr.
Month by month in Fairview
| Month | Avg high | Cooling degree days | AC kWh |
|---|---|---|---|
| Jan | 46.5°F | 0 | 0 |
| Feb | 51.3°F | 1 | 1 |
| Mar | 61.4°F | 10 | 14 |
| Apr | 71.3°F | 43 | 64 |
| May | 78°F | 138 | 203 |
| Jun | 85.2°F | 295 | 435 |
| Jul | 88.6°F | 419 | 617 |
| Aug | 87.9°F | 385 | 568 |
| Sep | 82.4°F | 210 | 310 |
| Oct | 70.8°F | 41 | 60 |
| Nov | 59.5°F | 3 | 5 |
| Dec | 49.8°F | 0 | 1 |
Jul alone uses 27% of the year's cooling energy. The unit runs the equivalent of 927 hours a year at full output.
Fairview against nearby cities
| City | Distance | Design day | Size for 2,000 sq ft |
|---|---|---|---|
| Dickson, TN | 15 mi | 92°F | 3 tons |
| Franklin, TN | 16 mi | 97°F | 3.5 tons |
| Brentwood, TN | 20 mi | 97°F | 3.5 tons |
| Spring Hill, TN | 20 mi | 95°F | 3 tons |
| Nashville-Davidson, TN | 23 mi | 97°F | 3.5 tons |
| Columbia, TN | 25 mi | 94°F | 3 tons |
Of 65 Tennessee cities here, Fairview has the 41st highest cooling load. The range runs from Crossville at 27,300 BTU/hr to Memphis at 41,200.
Where Fairview's weather numbers come from
The nearest NOAA station with full 1991 to 2020 normals is Fairview Bowie Nat Ctr, 1.1 miles from the center of Fairview at 860 ft above sea level. That is close enough that the station's summers are Fairview's summers.
No other city in this set uses Fairview Bowie Nat Ctr, so this sizing is Fairview's alone.
The sun over Fairview in late July
At 35.98°N, the noon sun on 21 July stands 74.4° above the horizon over Fairview and the day runs 14 h 05 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.
10,535 people live in Fairview, the 62nd largest of the 65 Tennessee cities sized on this site. Coordinates used: 35.9824, -87.1270.
Fairview AC sizing questions
What size AC does a 2,000 sq ft house in Fairview, TN need?
About 3 tons, for a cooling load of 35,100 BTU/hr on a 94°F design day. That is one ton per 683 square feet in Fairview's climate.
Is 20 BTU per square foot right for Fairview?
The chart gives 3.5 tons for 2,000 sq ft, against 3 tons sized from NOAA's 1991 to 2020 normals at Fairview Bowie Nat Ctr. For a single room here, plan on 17.6 BTU/hr per square foot.
What does central AC cost to run in Fairview?
About $314 a year: 2,278 kWh at SEER2 14.3 and 13.8¢ per kWh, over 5 cooling months.