ACSizeCheck

What size AC for Dublin, CA? 2.5 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Dublin needs

2.5 tons central AC or heat pump, about 29,200 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 44% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2.5 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 822 square feet in this climate. For a single room, size by the room: 14.6 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Livermore Municipal Airport (4.7 mi away). Jul is the hottest month, averaging a high of 87.7°F and a low of 56.6°F, with about 52 days a year at 90°F or more. That gives a design temperature of 93°F against 75°F inside.

What it costs to run

About 1,065 kWh a year at SEER2 14.3, or roughly $347 at California's average residential rate of 32.58¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Dublin

Of the 29,200 BTU/hr, 12,960 comes through walls, roof and windows on a 93°F afternoon (44%), 13,000 is sun on the house (45%), 2,120 is four people and their appliances, and 1,100 is moisture the coil has to wring out of Dublin's summer air (4%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 28,080 BTU/hr before the moisture allowance.

Other house sizes in Dublin

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft15,7001.5 tons2 tons
1,500 sq ft22,5002 tons2.5 tons
2,500 sq ft36,0003 tons5 tons
3,000 sq ft42,7004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,200 BTU/hr; a 350 sq ft living room needs about 5,100 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 8,800 BTU/hr.

Month by month in Dublin

MonthAvg highCooling degree daysAC kWh
Jan57.4°F00
Feb61°F00
Mar65.1°F00
Apr69.3°F810
May75.3°F4455
Jun82.6°F125157
Jul87.7°F226284
Aug87.5°F223280
Sep85.4°F170213
Oct77.9°F5265
Nov65.6°F11
Dec57.8°F00

Jul alone uses 27% of the year's cooling energy. The unit runs the equivalent of 522 hours a year at full output.

Dublin against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Pleasanton, CA3 mi93°F2.5 tons
San Ramon, CA4 mi93°F2.5 tons
Livermore, CA8 mi93°F2.5 tons
Danville, CA8 mi93°F2.5 tons
Union City, CA10 mi81°F2 tons
Hayward, CA13 mi81°F2 tons

Of 376 California cities here, Dublin has the 193rd highest cooling load. The range runs from Corte Madera at 15,700 BTU/hr to Palm Desert at 59,000.

Where Dublin's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Livermore Municipal Airport, 4.7 miles from the center of Dublin at 393 ft above sea level. That is close enough that the station's summers are Dublin's summers.

5 other cities use the same station and get the same climate inputs. The closest to Dublin: Pleasanton (3 mi away, 4 mi from the station), San Ramon (4 mi away, 8.1 mi from the station), Livermore (8 mi away, 3 mi from the station), Danville (8 mi away, 11.8 mi from the station), Brentwood (18 mi away, 17.6 mi from the station). Dublin is farther from the station than 2 of them.

The sun over Dublin in late July

At 37.72°N, the noon sun on 21 July stands 72.7° above the horizon over Dublin and the day runs 14 h 14 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

70,544 people live in Dublin, the 126th largest of the 376 California cities sized on this site. Coordinates used: 37.7161, -121.8962.

Dublin AC sizing questions

What size AC does a 2,000 sq ft house in Dublin, CA need?

About 2.5 tons, for a cooling load of 29,200 BTU/hr on a 93°F design day. That is one ton per 822 square feet in Dublin's climate.

Is 20 BTU per square foot right for Dublin?

The chart gives 3.5 tons for 2,000 sq ft, against 2.5 tons sized from NOAA's 1991 to 2020 normals at Livermore Municipal Airport. For a single room here, plan on 14.6 BTU/hr per square foot.

What does central AC cost to run in Dublin?

About $347 a year: 1,065 kWh at SEER2 14.3 and 32.58¢ per kWh, over 5 cooling months.