ACSizeCheck

What size AC for Centralia, IL? 3 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Centralia needs

3 tons central AC or heat pump, about 32,300 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 30% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 3 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 743 square feet in this climate. For a single room, size by the room: 16.1 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Iuka 12 Sw (8.5 mi away). Jul is the hottest month, averaging a high of 87.5°F and a low of 65.8°F, with about 33 days a year at 90°F or more. That gives a design temperature of 93°F against 75°F inside.

What it costs to run

About 1,739 kWh a year at SEER2 14.3, or roughly $334 at Illinois's average residential rate of 19.23¢ per kWh. Cooling runs 5 months of the year here.

What drives the load in Centralia

Of the 32,300 BTU/hr, 12,960 comes through walls, roof and windows on a 93°F afternoon (40%), 13,000 is sun on the house (40%), 2,120 is four people and their appliances, and 4,200 is moisture the coil has to wring out of Centralia's summer air (13%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 28,080 BTU/hr before the moisture allowance.

Other house sizes in Centralia

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft17,4001.5 tons2 tons
1,500 sq ft24,8002 tons2.5 tons
2,500 sq ft39,8003.5 tons5 tons
3,000 sq ft47,2004 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 2,400 BTU/hr; a 350 sq ft living room needs about 5,600 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 9,700 BTU/hr.

Month by month in Centralia

MonthAvg highCooling degree daysAC kWh
Jan38.8°F00
Feb44°F00
Mar54.2°F45
Apr66.2°F1926
May75.2°F96133
Jun84.1°F256356
Jul87.5°F362503
Aug86.9°F322447
Sep81°F157218
Oct69.3°F3548
Nov54.9°F23
Dec43.2°F00

Jul alone uses 29% of the year's cooling energy. The unit runs the equivalent of 770 hours a year at full output.

Centralia against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Mount Vernon, IL18 mi90°F2.5 tons
Highland, IL35 mi96°F3 tons
Shiloh, IL43 mi96°F3 tons
O'Fallon, IL43 mi96°F3 tons
Troy, IL44 mi96°F3 tons
Swansea, IL47 mi96°F3 tons

Of 225 Illinois cities here, Centralia has the 25th highest cooling load. The range runs from Fox Lake at 24,900 BTU/hr to Granite City at 36,000.

Where Centralia's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Iuka 12 Sw, 8.5 miles from the center of Centralia at 590 ft above sea level. That is close enough that the station's summers are Centralia's summers.

No other city in this set uses Iuka 12 Sw, so this sizing is Centralia's alone.

The sun over Centralia in late July

At 38.52°N, the noon sun on 21 July stands 71.9° above the horizon over Centralia and the day runs 14 h 18 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Shorter days give the house a longer night to shed the day's heat.

11,787 people live in Centralia, the 202nd largest of the 225 Illinois cities sized on this site. Coordinates used: 38.5221, -89.1235.

Centralia AC sizing questions

What size AC does a 2,000 sq ft house in Centralia, IL need?

About 3 tons, for a cooling load of 32,300 BTU/hr on a 93°F design day. That is one ton per 743 square feet in Centralia's climate.

Is 20 BTU per square foot right for Centralia?

The chart gives 3.5 tons for 2,000 sq ft, against 3 tons sized from NOAA's 1991 to 2020 normals at Iuka 12 Sw. For a single room here, plan on 16.1 BTU/hr per square foot.

What does central AC cost to run in Centralia?

About $334 a year: 1,739 kWh at SEER2 14.3 and 19.23¢ per kWh, over 5 cooling months.