ACSizeCheck

What size AC for Amherst, OH? 2 tons for 2,000 sq ft

What size AC a 2,000 sq ft house in Amherst needs

2 tons central AC or heat pump, about 25,700 BTU/hr of load

The 20 BTU per square foot chart would put in 3.5 tons, about 64% more than this climate needs. An oversized unit cools the air fast, shuts off before it pulls moisture out, and leaves the house cold and clammy.

If a contractor quotes you more than 2 tons for an average 2,000 sq ft house here, ask to see the Manual J load calculation behind it before you sign. That works out to one ton per 935 square feet in this climate. For a single room, size by the room: 12.8 BTU/hr per square foot.

The climate it is sized for

Climate from NOAA's 1991 to 2020 normals at Elyria Lorain County Airport (4.9 mi away). Jul is the hottest month, averaging a high of 82.3°F and a low of 62.2°F, with about 12 days a year at 90°F or more. That gives a design temperature of 87°F against 75°F inside.

What it costs to run

About 900 kWh a year at SEER2 14.3, or roughly $169 at Ohio's average residential rate of 18.81¢ per kWh. Cooling runs 4 months of the year here.

What drives the load in Amherst

Of the 25,700 BTU/hr, 8,640 comes through walls, roof and windows on a 87°F afternoon (34%), 13,000 is sun on the house (51%), 2,120 is four people and their appliances, and 1,900 is moisture the coil has to wring out of Amherst's summer air (7%).

Sun is the biggest share here, more than heat through the walls, so shading west windows and a light roof cut the size you need more than extra insulation would. Sensible heat totals 23,760 BTU/hr before the moisture allowance.

Other house sizes in Amherst

HouseLoad, BTU/hrSize20 BTU/ft² chart
1,000 sq ft14,0001.5 tons2 tons
1,500 sq ft19,8001.5 tons2.5 tons
2,500 sq ft31,5003 tons5 tons
3,000 sq ft37,3003.5 tons5 tons

Single rooms with a window or mini-split unit: a 150 sq ft bedroom needs about 1,900 BTU/hr; a 350 sq ft living room needs about 4,500 BTU/hr; a 600 sq ft open plan kitchen and family room needs about 7,700 BTU/hr.

Month by month in Amherst

MonthAvg highCooling degree daysAC kWh
Jan33.6°F00
Feb36.3°F00
Mar45.3°F12
Apr58.8°F68
May70°F4862
Jun79°F156204
Jul82.3°F230300
Aug79.9°F171223
Sep74.6°F6788
Oct62.6°F1114
Nov49.3°F00
Dec38.5°F00

Jul alone uses 33% of the year's cooling energy. The unit runs the equivalent of 502 hours a year at full output.

Amherst against nearby cities

CityDistanceDesign daySize for 2,000 sq ft
Lorain, OH4 mi87°F2 tons
Vermilion, OH4 mi87°F2 tons
Elyria, OH7 mi87°F2 tons
North Ridgeville, OH11 mi87°F2 tons
Avon, OH12 mi88°F2.5 tons
Avon Lake, OH13 mi88°F2.5 tons

Of 176 Ohio cities here, Amherst has the 163rd highest cooling load. The range runs from Conneaut at 24,100 BTU/hr to Hamilton at 31,500.

Where Amherst's weather numbers come from

The nearest NOAA station with full 1991 to 2020 normals is Elyria Lorain County Airport, 4.9 miles from the center of Amherst at 791 ft above sea level. That is close enough that the station's summers are Amherst's summers.

4 other cities use the same station and get the same climate inputs. The closest to Amherst: Lorain (4 mi away, 6.4 mi from the station), Vermilion (4 mi away, 8.3 mi from the station), Elyria (7 mi away, 4.4 mi from the station), North Ridgeville (11 mi away, 8.6 mi from the station). Amherst is farther from the station than 1 of them.

The sun over Amherst in late July

At 41.41°N, the noon sun on 21 July stands 69.0° above the horizon over Amherst and the day runs 14 h 33 min from sunrise to sunset. A lower noon sun puts more of the day's heat on east and west walls than on the roof, which is why shading west glass pays off here. Long days mean the house keeps gaining heat into the evening, well after the outdoor peak.

13,048 people live in Amherst, the 141st largest of the 176 Ohio cities sized on this site. Coordinates used: 41.4053, -82.2317.

Amherst AC sizing questions

What size AC does a 2,000 sq ft house in Amherst, OH need?

About 2 tons, for a cooling load of 25,700 BTU/hr on a 87°F design day. That is one ton per 935 square feet in Amherst's climate.

Is 20 BTU per square foot right for Amherst?

The chart gives 3.5 tons for 2,000 sq ft, against 2 tons sized from NOAA's 1991 to 2020 normals at Elyria Lorain County Airport. For a single room here, plan on 12.8 BTU/hr per square foot.

What does central AC cost to run in Amherst?

About $169 a year: 900 kWh at SEER2 14.3 and 18.81¢ per kWh, over 4 cooling months.